Crossworld Trading — a division of Crossworld Freighters LLC
Product group 04

From a 400 VA desktop unit to a 1.6 MVA modular frame.

Uninterruptible power supplies and battery systems for hospitals, data centres, airports, government facilities and commercial buildings — supplied in partnership with Amoori Trading, authorised reseller for Riello UPS and Schneider Electric (APC) in Saudi Arabia.

Before the model list

Three topologies, and they are not interchangeable.

Most UPS disappointment comes from buying the wrong topology rather than the wrong brand or the wrong size. IEC 62040-3 classifies them, so a specification can be written precisely.

VFI

Online double conversion

Mains is rectified to DC and re-inverted to AC continuously, so the load never sees the incoming supply. Zero transfer time and full conditioning. Required for anything where a few milliseconds matter — medical, data centre, process control.

VI

Line interactive

Runs the load on filtered mains and corrects voltage through an autotransformer, switching to battery only on failure. Efficient and cost-effective for offices, comms rooms and edge equipment tolerant of a short transfer.

VFD

Standby / offline

Passes mains straight through and switches to inverter on failure. The cheapest protection and appropriate for individual workstations — but not for anything a building depends on.

Riello UPS — single phase

Entry level and rack mount.

Workstations, comms cabinets, small server rooms and equipment racks.

Single-phase ranges
RangeRatingFormat
iPlug600 – 800 VAPlug-in desktop
iDialog400 – 1600 VATower
iDialog Rack600 – 1200 VARack mount
Net Power600 – 2000 VATower
Vision800 – 2000 VATower
Vision Rack800 – 1100 VARack mount
Vision Dual1.1 – 3 kVATower / rack convertible
Sentinel Pro700 – 3000 VATower, online
Sentinel Rack1.5 – 3 kVARack mount, online
Sentinel Tower1.5 – 3 kVATower, online
Riello UPS — mid range

Comms rooms to whole buildings.

Where the UPS starts serving a distribution board rather than a rack.

Mid-range ranges
RangeRatingNotes
Sentinel Dual (low power)1000 – 3000 VASingle and three-phase input options
Sentinel Dual SDU4 – 10 kVAOnline double conversion
Sentryum10 – 120 kVACompact three-phase
Sentryum Rack20 – 160 kVARack integrated
Master MPS10 – 200 kVAThree-phase
Master Industrial30 – 80 kVAIndustrial duty
Master FC40030 – 125 kVAThree-phase
Riello UPS — three phase

Data centre and critical infrastructure.

Modular and scalable frames where capacity is added in increments and redundancy is designed in from the start.

High-capacity three-phase ranges
RangeRatingNotes
Multi Sentry160 – 200 kVATransformer-based three-phase
Multi Power45 – 294 kVAModular
Multi Power 2300 – 600 kVAModular
Multi Power 2 Scalable1000 – 1600 kVAScalable modular frame
NextEnergy NXE250 – 800 kVAHigh efficiency
Master HP100 – 600 kVAHigh power
Master HE100 – 800 kVAHigh efficiency
Master HP UL65 – 500 kVAUL listed variant
Energy storage

What sits behind the inverter.

The battery decides the running cost, the footprint and how often someone has to come back. It is worth more attention than it usually gets.

01

VRLA sealed lead acid

The default. Lowest capital cost, widely available, well understood. Shorter design life and materially affected by ambient temperature — every few degrees above 20 °C shortens it, which matters a great deal in the Kingdom.

Lowest capex · temperature sensitive
02

Lithium

Higher capital cost, considerably longer service life, far smaller and lighter for the same autonomy, and much more tolerant of heat. Often the cheaper option measured across the life of the installation rather than the purchase order.

Long life · compact · heat tolerant
03

Supercapacitor

Very high cycle life and near-instant recharge, with short autonomy by design. Suited to ride-through duty where a generator picks up within seconds and the UPS only has to bridge the gap.

Ride-through · generator bridging
04

Autonomy & redundancy

Runtime is specified from the load profile and what happens next — orderly shutdown, generator start, or full ride-through. Parallel and N+1 configurations where a single frame failure must not take the load with it.

N+1 · parallel · runtime sizing
IEC 62040-1 safetyIEC 62040-2 EMC IEC 62040-3 performanceIEC 62040-4 environmental
Straight answer

Who stands behind the warranty.

Crossworld Trading supplies these systems in partnership with Amoori Trading LLC, who hold the authorised reseller appointment in Saudi Arabia for Riello UPS and Schneider Electric (APC). The manufacturer authorisation, warranty and factory-backed service sit with Amoori. Specification, pricing, import, clearance and delivery sit with us.

We are explicit about that split because a UPS is not a one-off purchase. It needs commissioning, battery replacement on a schedule, and someone contactable when it alarms at two in the morning. Knowing which company does which part before you buy is worth more than a slightly better price.

Riello UPS, Schneider Electric and APC are trademarks of their respective owners and are used here to identify the products supplied. Crossworld Trading is not itself an authorised reseller or agent for these manufacturers.

What to send for a sizing
  • Total load in kW, and the power factor if you know it
  • Required autonomy, and what happens at the end of it
  • Whether a generator backs the installation, and its start time
  • Single or three phase, and the available supply
  • Room temperature, ventilation and floor loading limits
  • Whether redundancy is required, and to what level
Request a sizing
Power protection

Tell us the load and the consequence of losing it.