Grades
Enhanced, standard, and alarm cable.
In a BS 5839-1 designed system the fire strategy decides which grade applies. Enhanced is not simply "better" — it is required in specific building types, and using standard grade there is a non-compliance.
01
Enhanced grade
The highest circuit-integrity classification: 930 °C for 120 minutes under simultaneous flame, mechanical impact and water spray. Specified where evacuation is phased or prolonged — high-rise towers, hospitals, unsprinklered buildings and critical government facilities.
BS 8434-2 · BS 6387 CWZ · PH120 + Annex E
02
Standard grade
Circuit integrity under flame and mechanical shock for the design evacuation period. The usual choice for fire detection and alarm, emergency lighting, public address and voice evacuation in buildings with a simultaneous evacuation strategy.
BS 6387 CWZ · EN 50200 PH30–PH120
03
Screened fire-resistant, 300/500 V
Multicore fire-resistant cable with aluminium or polyester tape screen and drain wire, for addressable loops and data-carrying life-safety circuits where the screen is needed against interference as well as fire.
BS 7629-1 · 2, 3 and 4 core · screened
04
Fire alarm cable, UL listed
Power-limited fire alarm cable to the North American convention, riser rated — flame height not exceeding 3.66 metres after thirty minutes of vertical burn. Supplied where the design follows NFPA rather than BS.
UL 1424 · UL 1666 · FPLR riser
05
Low smoke, zero halogen
Every grade above is available in LSZH construction. In an enclosed escape route the smoke and acid gas from burning cable can incapacitate people well before the fire reaches them, which is why LSZH is mandatory in most public buildings.
IEC 60754 halogen · IEC 61034-2 smoke
06
Armoured fire-resistant
Where a fire-rated circuit runs through plant rooms, risers or external routes and needs mechanical protection as well as circuit integrity. Available in solid and stranded conductor, screened or unscreened.
Armoured · solid or stranded · screened